           Federal Pacific Electric (FPE) Panels, a Summary

Information for building inspectors, home buyers, home owners, electricians exploring the background of possible hazards associated with Federal Pacific Electric Stab-lok circuit breakers and service panels.

Federal Pacific Electric "Stab-Lok" service panels and breakers are a latent hazard and can fail, leading to electrical fires. The problem is that some double-pole (240-Volt) FPE circuit breakers and possibly also some single-pole units simply may not work. We also have reports that independent of the breaker problems, there have been panel and panel-bus fires and arcing failures in some equipment. The failure rates for these circuit breakers were significant and are documented in the CPSC study.

Having reviewed documentation regarding this issue, and having discussed the issue with forensic experts in the field, I am convinced that a latent hazard exists where FPE Stab-Lok circuit breakers continue in use. The hazard is worst for double-pole breakers. Published reports of actual tests that were performed indicate that under certain conditions it is possible for one leg of these circuits to attempt to trip the breaker, resulting in a jammed breaker which will afterward not trip under any load condition. I infer from the Commission final press release in 1983 that the manufacturer and some Commission members were of the opinion that these conditions would not occur in the field.

This may be an erroneous conclusion. Some very common household appliances operate or are powered by a two-pole 240V circuit (protected by the type of breaker under discussion) but use two or more independent 120V sub-circuits inside the appliance. Two obvious cases are electric clothes dryers and ranges. If, for example, the low-heat (110V) heater in a dryer were to short to the dryer case, a serious over-current would occur on one "leg" of the circuit.

Another wiring practice, using a single two-pole breaker to power a split circuit which uses a shared neutral, such as may be installed in kitchens in some areas, is nearly certain to have each leg of the circuit loaded independently and thus subject to single-leg overloading and subsequent breaker jamming. A breaker which jams and then fails to trip under this condition is, in my opinion, a serious fire hazard.

A careful reading of the CPSC press release of March 3, 1984 suggests that the press release was very careful NOT to conclude that there is no hazard, but simply that the information at hand did not prove the hazard, and that the Commission did not have funds to pursue testing. In this document, the representation that no real hazard exists is made by the manufacturer of the device - not exactly a neutral party, and even that wording is cautious in tone: "FPE breakers will trip reliably at most overload levels." Readers should see the failure rates cited in the IAEI letter below.

It's the exceptions that cause fires.

Consumers should read and follow the Commission's advice regarding circuit breakers. But this advice is insufficient. The Commission's admonition to avoid overloading circuits and to turn off and have examined devices which seem to be creating a problem is a poor substitute for reliable, automatic, over-current protection. It is precisely because dangerous conditions can and do occur without adequate recognition and action by a consumer that circuit breakers and fuses are installed to provide over-current protection in the first place.

Therefore it is hardly an adequate "fix" for FPE breakers to just tell consumers to handle these cases manually.

It is possible that some breakers may perform with adequate reliability, possibly those manufactured after the companies discovered safety defects and improper practices in listing the product, and possibly those manufactured in Canada. However, in absence of an explicit statement from the manufacturer and/or the US CPSC indicating that newer stock equipment is defect free, and considering that defects occur in both breakers and the panels themselves, and finally, that testing showed failures in both in-use equipment and new off-the-shelf devices, my advice to consumers and electricians is that these panels be replaced with newer equipment, particularly those which use 240-volt double-pole breakers described in the literature. In my opinion, if a fire or other hazard occurs with this device, neither the manufacturer nor the Commission, who have suggested in the press release that data was inconclusive or inadequate to establish a hazard, will accept responsibility for losses that may ensue.

However a building inspector, home inspector, or contractor who makes any warranty of safety, by virtue of his/her position close to the consumer, is certain bear this very liability.

bulletOut of fairness to all parties, it's proper to describe this as a latent hazard. The panel does not "initiate" an unsafe condition. Rather, when an unsafe condition such as a short circuit or current overload on a circuit occurs, the equipment may not provide the protection expected. The result can be an overheated wire and an electrical fire and/or personal injury.

 
bulletIn addition to the information on-line, I have received a number of reports of panel overheating instances and related fires. It really happens. Some electricians have written to me that they call these "federal no-trip" panels.

 
bulletWhich is worse: a nervous buyer who understands that it's a legitimate concern that needs to be addressed, or a comfortable buyer who doesn't understand that and who later has an electrical fire that could have been prevented. Just ask: nervous vs. fire, nervous vs. fire, and figure out what's the professional responsible choice.

 
bulletThe fact that a problem has not occurred in a building is absolutely no assurance that questionable equipment is "safe." A circuit breaker has normally little to do except pass current onwards until there is an unsafe condition. If an unsafe condition has not occurred in a building the fact that a breaker may not trip is not discovered. If an over-current or short circuit subsequently occurs it's a bit late to discover that the circuit breaker did not do its job.

 For a more in depth source about FPE breakers go to: www.inspect-ny.com/fpe/fpepanel.htm